Nove funkcije #18831
Zatvorenapc na proxom-2 APC Smart ups 2200xl
Početak:
11.11.2009
Završetak:
% završeno:
0%
Procjena vremena:
Fajlovi
Izmjenjeno od Ernad Husremović prije više od 15 godina
proxmox-2
# apt-get install apcupsd
proxmox-2:/lib/modules# apctest
2009-11-11 15:09:35 apctest 3.14.4 (18 May 2008) debian Checking configuration ... Attached to driver: apcsmart sharenet.type = DISABLE cable.type = CUSTOM_SMART You are using a SMART cable type, so I'm entering SMART test mode mode.type = APCSMART_UPS Setting up the port ... Hello, this is the apcupsd Cable Test program. This part of apctest is for testing Smart UPSes. Please select the function you want to perform. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 1 I am going to run through the series of queries of the UPS that are used in initializing apcupsd. Simulating UPSlinkCheck ... Wrote: Y Got: SM Attempting to use smart_poll() ... Sent: Y Got: SM Good -- smart_poll() works!. Going to ask for valid commands... Protocol version is: 3 Alert characters are: !$%+?=#| Command characters are: ^A^N^Z+-789>@ABCDEFGKLMNOPQRSUVWXYZ'abcefgjklmnopqrsuxyz~^M Now running through apcupsd get_UPS capabilities(). NA indicates that the feature is Not Available UPS Status: 08 Line quality: FF Reason for last transfer to batteries: S Self-Test Status: NO Line Voltage: 226.2 Line Voltage Max: 228.8 Line Voltage Min: 224.9 Output Voltage: 226.2 Batt level percent: 100.0 Batt voltage: 55.65 UPS Load: 017.1 Line freq: 50.00 Runtime left: 0087 UPS Internal temp: 036.0 Dip switch settings: 00 Register 1: 00 Register 2: 00 Register 3: 00 Sensitivity: H Wakeup delay: 000 Sleep delay: 020 Low transfer voltage: 196 High transfer voltage: 253 Batt charge for return: 00 Alarm status: 0 Low battery shutdown level: 02 UPS Name: UPS_IDEN UPS Self test interval: 336 UPS manufacture date: 02/24/06 UPS serial number: QS0609310534 Date battery replaced: 02/24/06 Output voltage when on batteries: 230 Nominal battery voltage: 048 Percent humidity: NA Ambient temperature: NA Firmware revision: 81.14.I Number of external batteries installed: 000 Number of bad batteries installed: NA UPS model as defined by UPS: MWI UPS EPROM capabilities string: uD43132135138129uM43229234239224uA43110112114108uI43253264271280lD43103100097106lM43177172168182lA43090092081085lI43196188208204e44200155090oI43230240220225oD13115oJ13100oM13208s441HMLLq44202050710p443020180300600k4410TLNr443000060180300E443336168ON OFF The EPROM string is 253 characters long! Hours since last self test: NA That is all for now. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 2 First ensure that we have a good link and that the UPS is functionning normally. Simulating UPSlinkCheck ... Wrote: Y Got: SM Attempting to use smart_poll() ... Sent: Y Got: SM Good -- smart_poll() works!. Checking estimated runtime ... Current runtime is 87 minutes Checking for battery level ... Battery level is 100.0 -- OK The battery calibration should automatically end when the battery level drops below about 25, depending on your UPS. I can also optionally monitor the progress and stop the calibration if it goes below 10. However, in the case of a new battery this may prematurely end the calibration loosing the effect. Do you want me to stop the calibration if the battery level goes too low? (y/n): n Sending Battery Calibration command. ... UPS has initiated battery calibration. Monitoring the calibration progress ... To stop the calibration, enter a return. Battery charge 100 Remaining runtime is 87 minutes ..... Battery charge 97 Remaining runtime is 86 minutes .. User input. Terminating calibration ... Attempting to abort calibration ... Response to abort request: OK On battery 105 sec or 1m45s. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit
Izmjenjeno od Ernad Husremović prije više od 15 godina
- Naslov promijenjeno iz apc na proxom-2 u apc na proxom-2 APC Smart ups 2200xl
Izmjenjeno od Ernad Husremović prije više od 15 godina
external pack¶
That is all for now. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 6 Enter an ESC character (or ctl-[) to exit. YSM >000 +OK ^MNA >001
Izmjenjeno od Ernad Husremović prije više od 15 godina
bringout@vbox-karmic-i386-1:~$ irb
irb(main):001:0> 263/60.00 => 4.38333333333333
oooou on sad može 4 sahata radit'
Izmjenjeno od Ernad Husremović prije više od 15 godina
Sending Battery Calibration command. ... UPS has initiated battery calibration. Monitoring the calibration progress ... To stop the calibration, enter a return. Battery charge 100 Remaining runtime is 263 minutes ..... Battery charge 98 Remaining runtime is 258 minutes ..... Battery charge 98 Remaining runtime is 258 minutes .. User input. Terminating calibration ... Attempting to abort calibration ... Response to abort request: OK On battery 157 sec or 2m37s.
Izmjenjeno od Ernad Husremović prije više od 15 godina
- Fajl ASTE-6Z8LB2_R0_EN.pdf ASTE-6Z8LB2_R0_EN.pdf dodano
Izmjenjeno od Ernad Husremović prije oko 15 godina
- Status promijenjeno iz Dodijeljeno u Zatvoreno